NFPA 13 · Worked example

Double-interlock preaction pipe inventory

A preaction system has two Schedule 40 runs, 8 gallons of trim and a 26 psi supervisory setting.

Inputs

System arrangement
Pipe inventory
m
m
m
m
L

Include riser trim or vessels. Use zero length for unused pipe rows.

Air supply
bar
L/min
L/min

Supervisory pressure fill curve

Worksheet units
Edit inputs
Supervisory pressure fill curve · Input-linked engineering diagramSYSTEM VOLUME728.08LREQUIRED AIR54.26L/minFILL TIME11.09minAIR RESERVE73.16L/minAir · barFill curve30-min limit01.723.4503040Elapsed time · minCompressor vs. required air+73.16 L/min0 L/min54.26 L/min target108.53 L/min
Check timed water delivery

Preaction. Use the water-delivery criteria for the selected interlock.

How to read this example

Read the volume and air estimates. Apply the listed interlock’s delivery provisions separately from any dry-pipe allowance.

Open the base calculator

Calculated values

Total system volume
728.08 L
Pipe volume subtotal
697.8 L
Free air added from 0 psig
1.29 m³
Required free-air delivery
54.26 L/min
Modeled fill time
11.09 min
Compressor delivery reserve
73.16 L/min
Selected dry-pipe volume allowance
Timed delivery applies
Dry-pipe volume reserve
See delivery criteria
Pipe volume by run 4 rows
Pipe volume by run
RunInternal boremmLengthmVolumeL
1102.2651.8425.6
240.894207.3272.2
335.05200
426.64500

Equations and assumptions

  • V_pipe = Σ π d² L / 4
  • V_free = V_system × P_gauge / P_atm
  • FAD_30 = V_free / 30 + leakage

The non-dwelling dry-pipe volume screening paths are 500 gal without a quick-opening device or 750 gal with one. Larger volumes can use applicable timed delivery or listed calculation paths. Dwelling dry pipe and preaction require their own delivery criteria.

The isothermal fill starts at 0 psig with free air referenced to 14.696 psia. Use delivered compressor airflow at the target pressure and the valve manufacturer’s supervisory setpoint.

The 30-minute curve describes air restoration. Water delivery after sprinkler operation is evaluated separately.

Source references

Related examples