NFPA 13 · Worked example

Extra Hazard Group 1 with a larger orifice

A screening calculation uses 95 ft² per K8.0 sprinkler and 16 psi residual. Start with the 0.30 GPM/ft² reference density.

Inputs

Sprinkler head
L/min/√bar

Enter the listed K-factor in the selected units.

bar
bar

The calculation uses at least 7 psi (about 0.48 bar).

Density and coverage
m²

Remote sprinkler section

Worksheet units
Edit inputs
Remote sprinkler section · Input-linked engineering diagramDISCHARGE121.13L/minDENSITY FLOW107.88L/minMIN. PRESSURE0.88barFLOW RESERVE13.25L/minBRANCH LINEK 115.33 L/min/√barDensity 12.224 mm/min8.83 m² coverageDischarge vs. required flow+13.25 L/min0 L/min107.88 L/min target215.77 L/min
Flow and pressure targets met

Discharge and end-head pressure both meet the entered targets.

How to read this example

Switch units and compare the reference density and K-factor. Flow and area both change representation while the physical reserve stays fixed.

Open the base calculator

Calculated values

Delivered flow
121.13 L/min
Required density flow
107.88 L/min
Flow reserve
13.25 L/min
Required head pressure
0.88 bar
Minimum pressure floor
0.48 bar
Reserve above pressure floor
0.62 bar
Pressure for density alone
0.88 bar
Design density
12.224 mm/min
Hydraulic coverage at entered density
9.91 m²

Equations and assumptions

  • Q = K √P
  • Q_required = density × area
  • P_required = max(7 psi, listed minimum, (Q_required/K)²)

The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.

The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.

Source references