NFPA 13 · Worked example

Light-hazard hotel corridor

A standard spray head at the end of a hotel corridor covers 180 ft². The calculation leaves 13 psi at a K5.6 head.

Inputs

Sprinkler head
GPM/√psi

Enter the listed K-factor in the selected units.

psi
psi

The calculation uses at least 7 psi (about 0.48 bar).

Density and coverage
ft²

Remote sprinkler section

Worksheet units
Edit inputs
Remote sprinkler section · Input-linked engineering diagramDISCHARGE20.19GPMDENSITY FLOW18GPMMIN. PRESSURE10.33psiFLOW RESERVE2.19GPMBRANCH LINEK 5.6 GPM/√psiDensity 0.1 GPM/ft²180 ft² coverageDischarge vs. required flow+2.19 GPM0 GPM18 GPM target36 GPM
Flow and pressure targets met

Discharge and end-head pressure both meet the entered targets.

How to read this example

Compare the 18 GPM density target with the head discharge. The pressure wanted by the density calculation can be higher than the 7 psi floor.

Open the base calculator

Calculated values

Delivered flow
20.19 GPM
Required density flow
18 GPM
Flow reserve
2.19 GPM
Required head pressure
10.33 psi
Minimum pressure floor
7 psi
Reserve above pressure floor
6 psi
Pressure for density alone
10.33 psi
Design density
0.1 GPM/ft²
Hydraulic coverage at entered density
201.91 ft²

Equations and assumptions

  • Q = K √P
  • Q_required = density × area
  • P_required = max(7 psi, listed minimum, (Q_required/K)²)

The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.

The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.

Source references