NFPA 13
Sprinkler K-factor and density
Check the flow from a remote sprinkler against density × coverage area and its minimum operating pressure.
Inputs
Remote sprinkler section
Edit inputsFlow and pressure targets met
Discharge and end-head pressure both meet the entered targets.
Calculated values
- Delivered flow
- 22.4 GPM
- Required density flow
- 19.5 GPM
- Flow reserve
- 2.9 GPM
- Required head pressure
- 12.13 psi
- Minimum pressure floor
- 7 psi
- Reserve above pressure floor
- 9 psi
- Pressure for density alone
- 12.13 psi
- Design density
- 0.15 GPM/ft²
- Hydraulic coverage at entered density
- 149.33 ft²
Equations and assumptions
Q = K √PQ_required = density × areaP_required = max(7 psi, listed minimum, (Q_required/K)²)
The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.
The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.