NFPA 13 · Worked example
Extra Hazard Group 1 with a larger orifice
A screening calculation uses 95 ft² per K8.0 sprinkler and 16 psi residual. Start with the 0.30 GPM/ft² reference density.
Inputs
Remote sprinkler section
Edit inputsDischarge and end-head pressure both meet the entered targets.
How to read this example
Switch units and compare the reference density and K-factor. Flow and area both change representation while the physical reserve stays fixed.
Open the base calculatorCalculated values
- Delivered flow
- 121.13 L/min
- Required density flow
- 107.88 L/min
- Flow reserve
- 13.25 L/min
- Required head pressure
- 0.88 bar
- Minimum pressure floor
- 0.48 bar
- Reserve above pressure floor
- 0.62 bar
- Pressure for density alone
- 0.88 bar
- Design density
- 12.224 mm/min
- Hydraulic coverage at entered density
- 9.91 m²
Equations and assumptions
Q = K √PQ_required = density × areaP_required = max(7 psi, listed minimum, (Q_required/K)²)
The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.
The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.