NFPA 13 · Worked example
Light-hazard hotel corridor
A standard spray head at the end of a hotel corridor covers 180 ft². The calculation leaves 13 psi at a K5.6 head.
Inputs
Remote sprinkler section
Edit inputsDischarge and end-head pressure both meet the entered targets.
How to read this example
Compare the 18 GPM density target with the head discharge. The pressure wanted by the density calculation can be higher than the 7 psi floor.
Open the base calculatorCalculated values
- Delivered flow
- 20.19 GPM
- Required density flow
- 18 GPM
- Flow reserve
- 2.19 GPM
- Required head pressure
- 10.33 psi
- Minimum pressure floor
- 7 psi
- Reserve above pressure floor
- 6 psi
- Pressure for density alone
- 10.33 psi
- Design density
- 0.1 GPM/ft²
- Hydraulic coverage at entered density
- 201.91 ft²
Equations and assumptions
Q = K √PQ_required = density × areaP_required = max(7 psi, listed minimum, (Q_required/K)²)
The presets are common density/area design points for Light, Ordinary 1/2 and Extra 1/2. Pick the density for the adopted edition, occupancy and sprinkler listing.
The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.