Retaining wall stability

Resolve Rankine or Coulomb active thrust and check sliding, overturning and base contact.

Active thrust
43.3 kN/m
Sliding F.S.
1.61
Overturn F.S.
3.02
Eccentricity
0.234 m
Wall section & lateral pressure Schematic
Wall section & lateral pressure, schematic Backfill 0°Lateral pressureBase 2.5 mPₐ 43.3 kN/mGoverning limit ratio107.6%
  • Active pressure
  • Surcharge
  • Resultant

Sliding, overturning and middle-third screens all meet the displayed limits.

Calculation details
Active coefficient Ka0.307
Reference passive Kp (smooth, level toe)3.255
Effective retained height at heel3.4 m
Total horizontal driving force43.3 kN/m
Downward active force0 kN/m
Thrust height above base top1.27 m
Horizontal water thrust0 kN/m
Base uplift0 kN/m
Base width B2.5 m
Middle-third eccentricity limit B/60.417 m
Base resultant from toe1.016 m
Toe bearing pressure87.4 kPa
Heel bearing pressure24.5 kPa
Maximum contact pressure87.4 kPa
Minimum contact pressure24.5 kPa
Compression contact width2.5 m
Concrete stem weight24.48 kN/m
Concrete base weight21 kN/m
Soil weight over heel94.35 kN/m
Net downward load139.83 kN/m
Resisting moment about toe212.17 kN·m/m
Driving moment about toe70.15 kN·m/m

Inputs

Wall section
Backfill and interface
Groundwater behind wall

Engineering screening estimates. Use site-specific boring logs, appropriate test data and review by a licensed geotechnical PE before design or construction.

Method & assumptions

  1. Model the concrete and soil over the heel as a single gravity block. Apply active pressure on a vertical plane at the heel, where retained height is H + heel × tan β.
  2. For dry backfill, Pa = Ka(½γH² + qH) using the effective height at the heel. Soil thrust acts at one-third height and surcharge thrust at half height. Rankine inclines down by β. Coulomb uses the equivalent angle δ on the assumed heel plane.
  3. The reference Kp assumes level ground and a smooth passive plane. Water reduces effective soil pressure below its level and adds a separate horizontal hydrostatic triangle. The wet screen assumes no water in front and applies full heel water pressure uniformly under the base.
  4. Sliding F.S. = μV / Ph. Overturning F.S. is the ratio of resisting to driving moment about the toe. Positive eccentricity is toward the toe. Full contact uses V/B(1 ± 6e/B). Beyond the middle third, the base uses a compression-only triangle where a resultant remains within the base.
  5. Illustrative limits are 1.50 sliding and 2.00 overturning. Count base friction on net normal load, with zero passive resistance credit. Check site-specific bearing, global stability and the actual groundwater and uplift distribution.

Worked examples