GroundGridLab · Lee · legacy IEEE 1584
208 V panelboard screening case
A low-voltage panel uses the legacy panelboard distance exponent and a 25 mm gap. Low-voltage arc sustainability requires separate consideration.
Above thermal boundary level. Preliminary estimate at the working position. PPE category requires the separate NFPA 70E table method.
- Incident energy
- 7.343 J/cm²
- Arc-flash boundary
- 573.62 mm
- Time to boundary level
- 0.08205 s
- Working distance
- 455 mm
Inputs
| Equipment model | LV panelboard / MCC · legacy 1584 |
|---|---|
| System line-to-line voltage | 0.208 kV |
| Three-phase bolted fault current | 11 kA |
| Electrode gap | 25 mm |
| System grounding | Solidly grounded |
| Arc clearing time | 0.12 s |
| Working distance from arc | 455 mm |
Derived values
| Energy in both systems | 1.755 cal/cm² / 7.343 J/cm² |
|---|---|
| Reference energy bracket | ≤ 4 cal/cm² |
| NFPA 70E PPE category | Separate equipment tables |
| Boundary reference | 5.021 J/cm² |
| Clearing ceiling at 8 cal/cm² | 0.547 s |
| Clearing ceiling at 40 cal/cm² | 2.735 s |
| Legacy arcing current | 4.651 kA |
| Distance exponent | 1.641 |
Preliminary screening only. Use an IEEE 1584-2018 study, actual protective-device coordination and a qualified NFPA 70E assessment for equipment labeling, PPE or energized-work decisions.