GroundGridLab · Lee · legacy IEEE 1584
4.16 kV switchgear exposure
An MV lineup is screened using a 102 mm gap and a longer working distance. The model uses a legacy enclosure exponent.
Above thermal boundary level. Preliminary estimate at the working position. PPE category requires the separate NFPA 70E table method.
- Incident energy
- 20.99 J/cm²
- Arc-flash boundary
- 3,958.3 mm
- Time to boundary level
- 0.043057 s
- Working distance
- 910 mm
Inputs
| Equipment model | MV switchgear · legacy 1584 |
|---|---|
| System line-to-line voltage | 4.16 kV |
| Three-phase bolted fault current | 24 kA |
| Electrode gap | 102 mm |
| System grounding | Solidly grounded |
| Arc clearing time | 0.18 s |
| Working distance from arc | 910 mm |
Derived values
| Energy in both systems | 5.0166 cal/cm² / 20.99 J/cm² |
|---|---|
| Reference energy bracket | ≤ 8 cal/cm² |
| NFPA 70E PPE category | Separate equipment tables |
| Boundary reference | 5.021 J/cm² |
| Clearing ceiling at 8 cal/cm² | 0.28705 s |
| Clearing ceiling at 40 cal/cm² | 1.4352 s |
| Legacy arcing current | 22.95 kA |
| Distance exponent | 0.973 |
Preliminary screening only. Use an IEEE 1584-2018 study, actual protective-device coordination and a qualified NFPA 70E assessment for equipment labeling, PPE or energized-work decisions.