GroundGridLab · Dwight · uniform soil
Single service electrode
A 3 m vertical electrode with an 8 mm radius is installed in a uniform-soil screening model. The entered target is a project comparison value.
Resistance above target. The first count meeting the target in this layout is 3.
- Array resistance
- 33.493 Ω
- Single-rod resistance
- 33.493 Ω
- Array utilization
- 100 %
- Rods to reach target
- 3 rods
Inputs
| Native soil resistivity | 100 Ω·m |
|---|---|
| Driven rod length | 3 m |
| Rod radius | 8 mm |
| Backfill sleeve thickness | 0 mm |
| Rod layout | In-line row |
| Number of rods | 1 rods |
| Minimum rod centers | 3 m |
| Array resistance target | 15 Ω |
Derived values
| Bare single rod | 33.493 Ω |
|---|---|
| Ideal uncoupled array | 33.493 Ω |
| Coupling factor vs. ideal | 1 × |
| Center spacing / driven length | 1 × |
| Effective sleeve diameter | 16 mm |
| Maximum modeled count | 128 rods |
The sleeve is an ideal full-length cylinder. Uniform soil, perfect bonding and equal rod currents are assumed. Use field resistance tests and a layered model for design.