GroundGridLab · Dwight · uniform soil
Telecom shelter rod row
Four rods fit along the edge of an equipment shelter. A straight row makes spacing the main lever for reducing mutual coupling.
Resistance above target. The first count meeting the target in this layout is 6.
- Array resistance
- 13.019 Ω
- Single-rod resistance
- 40.191 Ω
- Array utilization
- 77.179 %
- Rods to reach target
- 6 rods
Inputs
| Native soil resistivity | 120 Ω·m |
|---|---|
| Driven rod length | 3 m |
| Rod radius | 8 mm |
| Backfill sleeve thickness | 0 mm |
| Rod layout | In-line row |
| Number of rods | 4 rods |
| Minimum rod centers | 3 m |
| Array resistance target | 10 Ω |
Derived values
| Bare single rod | 40.191 Ω |
|---|---|
| Ideal uncoupled array | 10.048 Ω |
| Coupling factor vs. ideal | 1.2957 × |
| Center spacing / driven length | 1 × |
| Effective sleeve diameter | 16 mm |
| Maximum modeled count | 128 rods |
The sleeve is an ideal full-length cylinder. Uniform soil, perfect bonding and equal rod currents are assumed. Use field resistance tests and a layered model for design.