GroundGridLab · IEEE 81 · four-point methods
Resistive rock beneath topsoil
A larger-spacing reading is being compared with a conductive topsoil layer over high-resistivity rock.
Resistivity rises with spacing. The trend follows the two assumed layers. The field reading is a separate apparent resistivity.
- Measured apparent ρₐ
- 252.68 Ω·m
- Model at field spacing
- 198.08 Ω·m
- Reflection factor K
- 0.86813
- Geometric factor
- 75.428 m
Inputs
| Electrode arrangement | Wenner 4-pin |
|---|---|
| Adjacent / potential pin spacing a | 12 m |
| Wenner pin burial depth b | 0.18 m |
| Measured V / I | 3.35 Ω |
| Upper-layer resistivity | 60 Ω·m |
| Lower-layer resistivity | 850 Ω·m |
| Upper-layer thickness | 4 m |
Derived values
| Apparent / predicted ratio | 1.2756 × |
|---|---|
| Model at 0.1× field spacing | 61.135 Ω·m |
| Model at 10× field spacing | 697.44 Ω·m |
| Upper / lower resistivity | 60 Ω·m / 850 Ω·m |
| Wenner depth multiplier | 1.0004 × |
Use a spacing series and independent traverses to estimate the layer parameters. Account for buried metal, moisture and survey uncertainty.