Worked example · IEEE 81 · four-point methods

Wenner survey with deep probes

Wenner and Schlumberger apparent resistivity with forward comparison against two assumed soil layers.

A short-spacing test uses deeply seated pins to maintain contact in dry gravel. The depth is substantial compared with the spacing.

Resistivity rises with spacing

The trend follows the two assumed layers. The field reading is a separate apparent resistivity.

Measured apparent ρₐ
232.6 Ω·m
Model at field spacing
181.92 Ω·m
Reflection factor K
0.4
Geometric factor
4.8459 m

Inputs

Field reading
m
m
Ω
Two-layer model
Ω·m
Ω·m
m

Four-pin survey & sounding curve

Live schematic
Measured ρₐ232.6 Ω·mModeled ρₐ181.9 Ω·mReflection K0.4Geometry4.846 mFOUR-PIN TRANSECTC1P1P2C2ρ₁ 180 Ω·mρ₂ 420 Ω·mAPPARENT ρ / Ω·m1442353840.060.66Pin spacing a / mObserved / modeled resistivity127.9%
The field lines are illustrative. The curve predicts a surface-electrode sounding for the entered two-layer profile.

Derived values & comparisons
Apparent / predicted ratio1.2786 ×
Model at 0.1× field spacing180 Ω·m
Model at 10× field spacing320.22 Ω·m
Upper / lower resistivity180 Ω·m / 420 Ω·m
Wenner depth multiplier1.2854 ×

Screening scope. Use a spacing series and independent traverses to estimate the layer parameters. Account for buried metal, moisture and survey uncertainty.

Try this. Compare the corrected reading with the zero-depth apparent resistivity.

Calculation method

IEEE Std 81-2012 §7.2.3, equations 2–3 and Annex A. Wenner uses 4πaR/[1 + 2a/√(a² + 4b²) − a/√(a² + b²)]. At b = 0 the result is 2πaR.

Schlumberger uses π(L − a/2)(L + a/2)R/a, where L is half the current-electrode span and a is the potential-electrode spacing. This geometry assumes shallow pins.

For the forward model, K = (ρ₂ − ρ₁)/(ρ₂ + ρ₁). Each image at depth 2nh contributes with weight Kⁿ. The series is evaluated for the two electrode distances and normalized by the homogeneous-soil geometric factor. The forward curve sweeps 0.1× to 10× the field spacing with a fixed array shape.

IEEE Std 81-2025 supersedes the 2012 guide. The published 2012 equations are the reference for this worksheet. Review the adopted edition for field procedures.

Standards and model assumptions