GroundGridLab · IEEE 81 · four-point methods
Uniform soil reference reading
Both assumed layer resistivities are identical. The expected forward sounding is flat at every spacing.
Uniform sounding. The trend follows the two assumed layers. The field reading is a separate apparent resistivity.
- Measured apparent ρₐ
- 100 Ω·m
- Model at field spacing
- 100 Ω·m
- Reflection factor K
- 0
- Geometric factor
- 31.416 m
Inputs
| Electrode arrangement | Wenner 4-pin |
|---|---|
| Adjacent / potential pin spacing a | 5 m |
| Wenner pin burial depth b | 0 m |
| Measured V / I | 3.1831 Ω |
| Upper-layer resistivity | 100 Ω·m |
| Lower-layer resistivity | 100 Ω·m |
| Upper-layer thickness | 3 m |
Derived values
| Apparent / predicted ratio | 1 × |
|---|---|
| Model at 0.1× field spacing | 100 Ω·m |
| Model at 10× field spacing | 100 Ω·m |
| Upper / lower resistivity | 100 Ω·m / 100 Ω·m |
| Wenner depth multiplier | 1 × |
Use a spacing series and independent traverses to estimate the layer parameters. Account for buried metal, moisture and survey uncertainty.