GroundGridLab · IEEE 81 · four-point methods
Wenner survey with deep probes
A short-spacing test uses deeply seated pins to maintain contact in dry gravel. The depth is substantial compared with the spacing.
Resistivity rises with spacing. The trend follows the two assumed layers. The field reading is a separate apparent resistivity.
- Measured apparent ρₐ
- 232.6 Ω·m
- Model at field spacing
- 181.92 Ω·m
- Reflection factor K
- 0.4
- Geometric factor
- 4.8459 m
Inputs
| Electrode arrangement | Wenner 4-pin |
|---|---|
| Adjacent / potential pin spacing a | 0.6 m |
| Wenner pin burial depth b | 0.28 m |
| Measured V / I | 48 Ω |
| Upper-layer resistivity | 180 Ω·m |
| Lower-layer resistivity | 420 Ω·m |
| Upper-layer thickness | 1.8 m |
Derived values
| Apparent / predicted ratio | 1.2786 × |
|---|---|
| Model at 0.1× field spacing | 180 Ω·m |
| Model at 10× field spacing | 320.22 Ω·m |
| Upper / lower resistivity | 180 Ω·m / 420 Ω·m |
| Wenner depth multiplier | 1.2854 × |
Use a spacing series and independent traverses to estimate the layer parameters. Account for buried metal, moisture and survey uncertainty.