Cooling tower approach, blowdown & makeup

Calculate wet-bulb approach and cooling range, then balance evaporation, drift, blowdown, and annual water use.

Evaporative tower water balance

Makeup = E + D + B · B = max(0, E/(CoC − 1) − D)

Edit inputs ↓
Approach
5K
Range
9K
Makeup flow
98.496L/min
Annual cost
68.61KUSD/yr
Evaporative tower water balanceEDBHOT WATERCOLD WATER38 °C29 °CWet bulb24 °C03 K screen10 K
The E, D, and B bars show evaporation, drift, and blowdown as shares of makeup. The approach bar compares cold water with entering wet bulb.
  • Within the displayed screening checks.

Inputs

L/min
°C
°C
°C
%/K
%
h/yr
USD/m³

Calculated results

Wet-bulb approach
5 K
Water cooling range
9 K
Makeup flow
98.496 L/min
Annual water cost
68,612 USD/yr
Evaporation loss
73.872 L/min
Drift loss
0.114 L/min
Blowdown flow
24.51 L/min
Achievable concentration cycles
4
Annual makeup volume
31,913 m³/yr
Approximate heat rejection
3,566.8 kW

Calculation basis

Range is hot minus cold water. Approach is cold water minus entering wet bulb. The approximate rejection load uses 998 kg/m³ and 4.18 kJ/kg·K for water.

The default evaporation factor is 0.08% of circulation per °F of range. Drift is an entered fraction of circulation. Cycles use a steady-state dissolved-solids balance with zero mineral loss through evaporation.

If drift meets or exceeds the permissible concentrated water loss, blowdown is zero and attainable cycles can be below the target. Annual cost multiplies makeup flow by entered run hours and the water price.