Cooling tower approach, blowdown & makeup
Calculate wet-bulb approach and cooling range, then balance evaporation, drift, blowdown, and annual water use.
Evaporative tower water balance
Makeup = E + D + B · B = max(0, E/(CoC − 1) − D)
- Approach
- 5K
- Range
- 9K
- Makeup flow
- 98.496L/min
- Annual cost
- 68.61KUSD/yr
- Within the displayed screening checks.
Inputs
Calculated results
- Wet-bulb approach
- 5 K
- Water cooling range
- 9 K
- Makeup flow
- 98.496 L/min
- Annual water cost
- 68,612 USD/yr
- Evaporation loss
- 73.872 L/min
- Drift loss
- 0.114 L/min
- Blowdown flow
- 24.51 L/min
- Achievable concentration cycles
- 4
- Annual makeup volume
- 31,913 m³/yr
- Approximate heat rejection
- 3,566.8 kW
Calculation basis
Range is hot minus cold water. Approach is cold water minus entering wet bulb. The approximate rejection load uses 998 kg/m³ and 4.18 kJ/kg·K for water.
The default evaporation factor is 0.08% of circulation per °F of range. Drift is an entered fraction of circulation. Cycles use a steady-state dissolved-solids balance with zero mineral loss through evaporation.
If drift meets or exceeds the permissible concentrated water loss, blowdown is zero and attainable cycles can be below the target. Annual cost multiplies makeup flow by entered run hours and the water price.
Methodology and references