Concentration cycles limited by drift
An older tower with high drift targets a concentration ratio that would require negative blowdown.
Evaporative tower water balance
Makeup = E + D + B · B = max(0, E/(CoC − 1) − D)
- Approach
- 5K
- Range
- 4K
- Makeup flow
- 31.363L/min
- Annual cost
- 19.87KUSD/yr
- Drift limits achievable cycles even with blowdown fully closed.
Inputs
Calculated results
- Wet-bulb approach
- 5 K
- Water cooling range
- 4 K
- Makeup flow
- 31.363 L/min
- Annual water cost
- 19,872 USD/yr
- Evaporation loss
- 24.883 L/min
- Drift loss
- 6.48 L/min
- Blowdown flow
- 0 L/min
- Achievable concentration cycles
- 4.84
- Annual makeup volume
- 9,032.6 m³/yr
- Approximate heat rejection
- 1,201.4 kW
Worked solution
Preset calculation · Metric SI
- Find 4 K range from the water temperatures and 5 K approach from cold water and entering wet bulb.
- Calculate 24.883 L/min evaporation and 6.48 L/min drift. The solids balance gives 0 L/min blowdown.
- Add the three losses to get 31.363 L/min makeup. With the given hours and tariff, the annual cost is 19,872 USD/yr.
Blowdown clamps at zero. Read attainable cycles to see what the existing drift loss permits.
Calculation basis
Range is hot minus cold water. Approach is cold water minus entering wet bulb. The approximate rejection load uses 998 kg/m³ and 4.18 kJ/kg·K for water.
The default evaporation factor is 0.08% of circulation per °F of range. Drift is an entered fraction of circulation. Cycles use a steady-state dissolved-solids balance with zero mineral loss through evaporation.
If drift meets or exceeds the permissible concentrated water loss, blowdown is zero and attainable cycles can be below the target. Annual cost multiplies makeup flow by entered run hours and the water price.
Methodology and references