Seasonal production water budget
A campaign-driven process runs its cooling tower for part of the year and budgets water at a combined tariff.
Evaporative tower water balance
Makeup = E + D + B · B = max(0, E/(CoC − 1) − D)
- Approach
- 6K
- Range
- 10K
- Makeup flow
- 308.7L/min
- Annual cost
- 237.7KUSD/yr
- Within the displayed screening checks.
Inputs
Calculated results
- Wet-bulb approach
- 6 K
- Water cooling range
- 10 K
- Makeup flow
- 308.7 L/min
- Annual water cost
- 237,680 USD/yr
- Evaporation loss
- 220.5 L/min
- Drift loss
- 0.294 L/min
- Blowdown flow
- 87.906 L/min
- Achievable concentration cycles
- 3.5
- Annual makeup volume
- 54,640 m³/yr
- Approximate heat rejection
- 10,221 kW
Worked solution
Preset calculation · Metric SI
- Find 10 K range from the water temperatures and 6 K approach from cold water and entering wet bulb.
- Calculate 220.5 L/min evaporation and 0.294 L/min drift. The solids balance gives 87.906 L/min blowdown.
- Add the three losses to get 308.7 L/min makeup. With the given hours and tariff, the annual cost is 237,680 USD/yr.
Vary run hours to change annual water volume and cost while instantaneous makeup stays fixed.
Calculation basis
Range is hot minus cold water. Approach is cold water minus entering wet bulb. The approximate rejection load uses 998 kg/m³ and 4.18 kJ/kg·K for water.
The default evaporation factor is 0.08% of circulation per °F of range. Drift is an entered fraction of circulation. Cycles use a steady-state dissolved-solids balance with zero mineral loss through evaporation.
If drift meets or exceeds the permissible concentrated water loss, blowdown is zero and attainable cycles can be below the target. Annual cost multiplies makeup flow by entered run hours and the water price.
Methodology and references