Tight approach at summer design wet bulb
Summer humidity puts the desired cold-water supply close to the entering wet-bulb temperature.
Evaporative tower water balance
Makeup = E + D + B · B = max(0, E/(CoC − 1) − D)
- Approach
- 2K
- Range
- 10.5K
- Makeup flow
- 215.46L/min
- Annual cost
- 135.7KUSD/yr
- Approach is below 3 K. Confirm tower selection at this wet-bulb condition.
Inputs
Calculated results
- Wet-bulb approach
- 2 K
- Water cooling range
- 10.5 K
- Makeup flow
- 215.46 L/min
- Annual water cost
- 135,740 USD/yr
- Evaporation loss
- 172.37 L/min
- Drift loss
- 0.171 L/min
- Blowdown flow
- 42.921 L/min
- Achievable concentration cycles
- 5
- Annual makeup volume
- 54,296 m³/yr
- Approximate heat rejection
- 8,322.4 kW
Worked solution
Preset calculation · Metric SI
- Find 10.5 K range from the water temperatures and 2 K approach from cold water and entering wet bulb.
- Calculate 172.37 L/min evaporation and 0.171 L/min drift. The solids balance gives 42.921 L/min blowdown.
- Add the three losses to get 215.46 L/min makeup. With the given hours and tariff, the annual cost is 135,740 USD/yr.
The 2 K approach falls below the screening threshold. Compare with a warmer cold-water setpoint and read the updated water use.
Calculation basis
Range is hot minus cold water. Approach is cold water minus entering wet bulb. The approximate rejection load uses 998 kg/m³ and 4.18 kJ/kg·K for water.
The default evaporation factor is 0.08% of circulation per °F of range. Drift is an entered fraction of circulation. Cycles use a steady-state dissolved-solids balance with zero mineral loss through evaporation.
If drift meets or exceeds the permissible concentrated water loss, blowdown is zero and attainable cycles can be below the target. Annual cost multiplies makeup flow by entered run hours and the water price.