Worked example

Ambient temperature above the oil target

When the surroundings are hotter than target oil, the tank adds heat. The entered ETD represents a cooler with a colder external heat sink.

Inputs

HP
%
Useful power divided by shaft input over the duty cycle.
GPM
°F
°F
ft²
BTU/hr·ft²·°F
Typical bare-steel starting estimate is 2–2.5 BTU/hr·ft²·°F.
°F
Oil inlet temperature minus coolant inlet temperature at the cooler.

Anatomy

Hydraulic power unit thermal balance
Hydraulic power unit thermal balanceCIRCUIT HEAT25.4kBTU/hrTANK HEAT-675BTU/hrCOOLER LOAD26.1kBTU/hrMIN. TANK60galPumpLoadCoolerReservoirHeat inPressureReturnTank / suctionCooler load / circuit heat102.7%0%100% reference150%

Results

US customary

Ambient temperature meets or exceeds the oil target. An ambient-air cooler cannot achieve this target. Check a colder heat sink.

Circuit heat generation25,444.336BTU/hr7.457kW
Oil target minus ambient-10°F
Passive tank rejection-675BTU/hr-0.198kW
Required cooler heat removal26,119.336BTU/hr7.655kW
Net heat · horsepower equivalent10.265HP7.655kW
Cooler rating at entered ETD652.9834BTU/hr/°F0.3445kW/°C
Reservoir guide · 3 min60gal
Reservoir guide · 5 min100gal

Worked calculation

  1. Heat generation

    Heat in = shaft input × (1 − duty-weighted efficiency). Use average shaft power across the same duty cycle.

  2. Reservoir heat rejection

    Tank heat out = h × exposed area × (T_oil − T_ambient). A negative result means the surroundings add heat.

  3. Cooler capacity and reservoir volume

    Cooler load = max(0, heat in − tank heat out). Required cooler rating = load/ETD. The 3–5 minute volume guide is 3–5 gal per GPM or 3–5 L per LPM.

Results for the original example inputs
Circuit heat generation25,444.336BTU/hr
Passive tank rejection-675BTU/hr
Required cooler heat removal26,119.336BTU/hr
Cooler rating at entered ETD652.9834BTU/hr/°F
Reservoir guide · 3 min60gal
Reservoir guide · 5 min100gal

Steady thermal balance at the entered target oil temperature. OEM cooler ratings depend on oil viscosity, coolant and oil flow, fan airflow, fouling and allowable pressure drop. Size tank working volume for deaeration, return levels and cylinder drawdown.

The calculator uses US fluid-power conventions for mechanical horsepower and US gallons, and SI base units for the model. See the methodology and rounding rules.