Worked example

Cooler with a small entering difference

A reduced ETD increases the required capacity per degree for the same oil heat load. Compare with the OEM rating at the entered oil flow.

Inputs

HP
%
Useful power divided by shaft input over the duty cycle.
GPM
°F
°F
ft²
BTU/hr·ft²·°F
Typical bare-steel starting estimate is 2–2.5 BTU/hr·ft²·°F.
°F
Oil inlet temperature minus coolant inlet temperature at the cooler.

Anatomy

Hydraulic power unit thermal balance
Hydraulic power unit thermal balanceCIRCUIT HEAT16.8kBTU/hrTANK HEAT2300BTU/hrCOOLER LOAD14.5kBTU/hrMIN. TANK36galPumpLoadCoolerReservoirTank heatPressureReturnTank / suctionCooler load / circuit heat86.3%0%100% reference150%

Results

US customary
Circuit heat generation16,793.262BTU/hr4.922kW
Oil target minus ambient50°F
Passive tank rejection2,300BTU/hr0.674kW
Required cooler heat removal14,493.262BTU/hr4.248kW
Net heat · horsepower equivalent5.696HP4.248kW
Cooler rating at entered ETD966.2174BTU/hr/°F0.5097kW/°C
Reservoir guide · 3 min36gal
Reservoir guide · 5 min60gal

Worked calculation

  1. Heat generation

    Heat in = shaft input × (1 − duty-weighted efficiency). Use average shaft power across the same duty cycle.

  2. Reservoir heat rejection

    Tank heat out = h × exposed area × (T_oil − T_ambient). A negative result means the surroundings add heat.

  3. Cooler capacity and reservoir volume

    Cooler load = max(0, heat in − tank heat out). Required cooler rating = load/ETD. The 3–5 minute volume guide is 3–5 gal per GPM or 3–5 L per LPM.

Results for the original example inputs
Circuit heat generation16,793.262BTU/hr
Passive tank rejection2,300BTU/hr
Required cooler heat removal14,493.262BTU/hr
Cooler rating at entered ETD966.2174BTU/hr/°F
Reservoir guide · 3 min36gal
Reservoir guide · 5 min60gal

Steady thermal balance at the entered target oil temperature. OEM cooler ratings depend on oil viscosity, coolant and oil flow, fan airflow, fouling and allowable pressure drop. Size tank working volume for deaeration, return levels and cylinder drawdown.

The calculator uses US fluid-power conventions for mechanical horsepower and US gallons, and SI base units for the model. See the methodology and rounding rules.