Worked example
30 HP hydraulic power unit
Subtract tank heat rejection from average circuit losses. Divide the remaining load by the 50 °F cooler entering temperature difference.
Inputs
Anatomy
Hydraulic power unit thermal balanceResults
US customary| Circuit heat generation | 16,793.262BTU/hr4.922kW |
|---|---|
| Oil target minus ambient | 55°F |
| Passive tank rejection | 3,217.5BTU/hr0.943kW |
| Required cooler heat removal | 13,575.762BTU/hr3.979kW |
| Net heat · horsepower equivalent | 5.335HP3.979kW |
| Cooler rating at entered ETD | 271.5152BTU/hr/°F0.1432kW/°C |
| Reservoir guide · 3 min | 48gal |
| Reservoir guide · 5 min | 80gal |
Worked calculation
Heat generation
Heat in = shaft input × (1 − duty-weighted efficiency). Use average shaft power across the same duty cycle.
Reservoir heat rejection
Tank heat out = h × exposed area × (T_oil − T_ambient). A negative result means the surroundings add heat.
Cooler capacity and reservoir volume
Cooler load = max(0, heat in − tank heat out). Required cooler rating = load/ETD. The 3–5 minute volume guide is 3–5 gal per GPM or 3–5 L per LPM.
| Circuit heat generation | 16,793.262BTU/hr |
|---|---|
| Passive tank rejection | 3,217.5BTU/hr |
| Required cooler heat removal | 13,575.762BTU/hr |
| Cooler rating at entered ETD | 271.5152BTU/hr/°F |
| Reservoir guide · 3 min | 48gal |
| Reservoir guide · 5 min | 80gal |
Steady thermal balance at the entered target oil temperature. OEM cooler ratings depend on oil viscosity, coolant and oil flow, fan airflow, fouling and allowable pressure drop. Size tank working volume for deaeration, return levels and cylinder drawdown.
The calculator uses US fluid-power conventions for mechanical horsepower and US gallons, and SI base units for the model. See the methodology and rounding rules.