208 V industrial capacitor branch

An industrial 208 V distribution panel supplies a 42 kW inductive load at 0.66 PF. The correction target is 0.90.

Inputs

Load & bank
Enter the three-phase short-circuit MVA at the bank. Use 0 to omit resonance screening.
Utility penalty

Reactive compensation and capacity

60 Hz · US customaryEdit inputs
Reactive compensation and capacity at 60 Hz BANK SIZE27.47kVARPER PHASE561.33µFFREED KVA16.97kVAPAYBACK11.3moBefore and after correctionCorrectedOriginalTransformer capacityBefore correction63.64 kVAAfter correction46.67 kVAReleased capacity16.97 kVACurrent reduction26.7%of original

Detailed results
Reactive compensation
27.47 kVAR
Capacitance per phase
561.33 µF
Voltage across each capacitor
208 V
Line current reduction
26.67%
Transformer capacity freed
16.97 kVA
Apparent power before
63.64 kVA
Apparent power after
46.67 kVA
Reactive power before
47.81 kVAR
Reactive power after
20.34 kVAR
Line current before
176.64 A
Line current after
129.53 A
Monthly penalty reduction
230 USD/mo
Simple payback
11.3 mo
Estimated parallel resonance order
Unavailable
Estimated parallel resonance frequency
Unavailable

Worked calculation

Use the reactive power difference at 42 kW, then divide by the squared 208 V capacitor voltage in the Delta capacitance equation. Lower voltage requires greater capacitance at the same kVAR.

Reactive compensation
27.47 kVAR
Capacitance per phase
561.33 µF
Line current reduction
26.67%

Values in this solution use the original example inputs.

Formulas & assumptions

Required reactive power

Q_C = P · [tan(acos(PF₁)) − tan(acos(PF₂))]

Active kW stays constant. Use lagging power factors with the target at least as high as the original. Upstream apparent power falls from P/PF₁ to P/PF₂.

Three equal capacitors

C_phase = Q_C · 10⁹ / (3 · 2πf · V_C²) [µF]

Use V_C = V_LL for Delta and V_LL/√3 for Wye. Wye requires three times the capacitance per phase at equal kVAR, line voltage, and frequency.

Parallel resonance

h₀ ≈ √(1000 · MVA_sc / Q_C); f₀ = f · h₀

Screen an undetuned bank on a predominantly inductive source. An alert within 0.5 of an odd order from 3 to 13 flags a case for spectrum and switching-step review. Check other orders and actual bus configurations.

Current and payback

I = 1000 · S / (√3 · V_LL), payback = installed cost / monthly penalty reduction

Enter the tariff penalty for each condition. A positive reduction with a nonzero bank is required for a simple payback. The currency selector changes units only.

Balanced sinusoidal load. Compare manufacturer voltage, step size, inrush and switching duties. Review harmonics, resonance, and light-load overcompensation before choosing a bank.

Engineering references

More worked examples