Required reactive power
Q_C = P · [tan(acos(PF₁)) − tan(acos(PF₂))]
Active kW stays constant. Use lagging power factors with the target at least as high as the original. Upstream apparent power falls from P/PF₁ to P/PF₂.
A 125 kW compressor group is already at its 0.95 target.
The two tangent terms are equal. Bank kVAR and capacitance are zero, and the before/after current is identical.
Values in this solution use the original example inputs.
Q_C = P · [tan(acos(PF₁)) − tan(acos(PF₂))]
Active kW stays constant. Use lagging power factors with the target at least as high as the original. Upstream apparent power falls from P/PF₁ to P/PF₂.
C_phase = Q_C · 10⁹ / (3 · 2πf · V_C²) [µF]
Use V_C = V_LL for Delta and V_LL/√3 for Wye. Wye requires three times the capacitance per phase at equal kVAR, line voltage, and frequency.
h₀ ≈ √(1000 · MVA_sc / Q_C); f₀ = f · h₀
Screen an undetuned bank on a predominantly inductive source. An alert within 0.5 of an odd order from 3 to 13 flags a case for spectrum and switching-step review. Check other orders and actual bus configurations.
I = 1000 · S / (√3 · V_LL), payback = installed cost / monthly penalty reduction
Enter the tariff penalty for each condition. A positive reduction with a nonzero bank is required for a simple payback. The currency selector changes units only.
Balanced sinusoidal load. Compare manufacturer voltage, step size, inrush and switching duties. Review harmonics, resonance, and light-load overcompensation before choosing a bank.