Correction without penalty savings

A 415 V process area wants extra transformer capacity even though its current tariff has no PF penalty.

Inputs

Load & bank
Enter the three-phase short-circuit MVA at the bank. Use 0 to omit resonance screening.
Utility penalty

Reactive compensation and capacity

50 Hz · MetricEdit inputs
Reactive compensation and capacity at 50 Hz BANK SIZE83.82kVARPER PHASE516.4µFFREED KVA42.28kVAPAYBACK—Before and after correctionCorrectedOriginalTransformer capacityBefore correction233.77 kVAAfter correction191.49 kVAReleased capacity42.28 kVACurrent reduction18.1%of original
  • Simple payback requires a positive monthly penalty reduction.

Detailed results
Reactive compensation
83.82 kVAR
Capacitance per phase
516.4 µF
Voltage across each capacitor
415 V
Line current reduction
18.09%
Transformer capacity freed
42.28 kVA
Apparent power before
233.77 kVA
Apparent power after
191.49 kVA
Reactive power before
149.15 kVAR
Reactive power after
65.33 kVAR
Line current before
325.22 A
Line current after
266.4 A
Monthly penalty reduction
0 GBP/mo
Simple payback
Unavailable
Estimated parallel resonance order
Unavailable
Estimated parallel resonance frequency
Unavailable

Worked calculation

Compute kVAR for 180 kW from 0.77 to 0.94. Both penalty inputs are zero, so the economics section has zero savings and no finite payback.

Reactive compensation
83.82 kVAR
Transformer capacity freed
42.28 kVA
Simple payback
Unavailable

Values in this solution use the original example inputs.

Formulas & assumptions

Required reactive power

Q_C = P · [tan(acos(PF₁)) − tan(acos(PF₂))]

Active kW stays constant. Use lagging power factors with the target at least as high as the original. Upstream apparent power falls from P/PF₁ to P/PF₂.

Three equal capacitors

C_phase = Q_C · 10⁹ / (3 · 2πf · V_C²) [µF]

Use V_C = V_LL for Delta and V_LL/√3 for Wye. Wye requires three times the capacitance per phase at equal kVAR, line voltage, and frequency.

Parallel resonance

h₀ ≈ √(1000 · MVA_sc / Q_C); f₀ = f · h₀

Screen an undetuned bank on a predominantly inductive source. An alert within 0.5 of an odd order from 3 to 13 flags a case for spectrum and switching-step review. Check other orders and actual bus configurations.

Current and payback

I = 1000 · S / (√3 · V_LL), payback = installed cost / monthly penalty reduction

Enter the tariff penalty for each condition. A positive reduction with a nonzero bank is required for a simple payback. The currency selector changes units only.

Balanced sinusoidal load. Compare manufacturer voltage, step size, inrush and switching duties. Review harmonics, resonance, and light-load overcompensation before choosing a bank.

Engineering references