Three-phase power & Wye/Delta calculator

Calculate kW, kVA, kVAR, line and winding quantities, and unbalanced Wye neutral current from AC voltage, current, and power factor.

Inputs

Supply & load
Enter the selected voltage reference. Delta uses line-to-line voltage.
Neutral study

Power triangle and phase currents

60 Hz · US customaryEdit inputs
Power triangle and phase currents at 60 Hz REAL POWER85.8kWAPPARENT99.77kVAREACTIVE50.91kVARNEUTRAL0AComplex powerφ 30.7°P · kWQ · kVARS · kVALine current phasorsYL1L2L3N sumNeutral current0 A120 A ref.

Detailed results
Real power
85.8 kW
Apparent power
99.77 kVA
Signed reactive power
50.91 kVAR
Signed phase angle
30.68°
Line-to-line voltage
480 V
Line-to-neutral voltage
277.13 V
Winding voltage
277.13 V
Line current
120 A
Winding current
120 A
Neutral RMS current
0 A
Single-phase apparent power at equal V & A
57.6 kVA
Single-phase real power at equal V & A
49.54 kW

Formulas & assumptions

Apparent, real and reactive power

S = √3 · V_LL · I_L / 1000, P = S · PF, Q = S · sin φ

For a balanced three-phase load, use RMS line quantities. For single-phase, replace √3 with 1 and use the applied voltage. φ = acos(PF) for lagging current and −acos(PF) for leading current.

Wye and Delta winding quantities

Y: V_w = V_LL / √3, I_w = I_L. Δ: V_w = V_LL, I_w = I_L / √3.

In four-wire Wye, winding voltage equals line-to-neutral voltage. The balanced Delta model has three wires and no line-to-neutral output. For single-phase, choose line-to-line or line-to-neutral according to the two supply terminals.

Optional Wye neutral vector

I_N = |I_A + I_B∠−120° + I_C∠+120°|

The neutral magnitude uses three fundamental RMS currents spaced 120° apart with the same displacement angle. The balanced power calculation is independent of these entries. Harmonic neutral loading uses the harmonic calculator.

Sinusoidal steady-state RMS with L1–L2–L3 positive sequence. The phasor arrows are line currents on an ideal phase reference. Delta winding current follows the magnitude relation shown above.

Engineering references

Worked examples