400 V, 50 Hz Wye load

A metric plant board supplies 84 A at 0.91 lagging PF from a balanced 400 V, 50 Hz system.

Inputs

Supply & load
Enter the selected voltage reference. Delta uses line-to-line voltage.
Neutral study

Power triangle and phase currents

50 Hz · MetricEdit inputs
Power triangle and phase currents at 50 Hz REAL POWER52.96kWAPPARENT58.2kVAREACTIVE24.13kVARNEUTRAL0AComplex powerφ 24.5°P · kWQ · kVARS · kVALine current phasorsYL1L2L3N sumNeutral current0 A84 A ref.

Detailed results
Real power
52.96 kW
Apparent power
58.2 kVA
Signed reactive power
24.13 kVAR
Signed phase angle
24.49°
Line-to-line voltage
400 V
Line-to-neutral voltage
230.94 V
Winding voltage
230.94 V
Line current
84 A
Winding current
84 A
Neutral RMS current
0 A
Single-phase apparent power at equal V & A
33.6 kVA
Single-phase real power at equal V & A
30.58 kW

Worked calculation

The winding sees 400/√3 V. Apparent power uses 400 V and all three line currents. Apply 0.91 to the kVA to find kW.

Winding voltage
230.94 V
Apparent power
58.2 kVA
Real power
52.96 kW

Values in this solution use the original example inputs.

Formulas & assumptions

Apparent, real and reactive power

S = √3 · V_LL · I_L / 1000, P = S · PF, Q = S · sin φ

For a balanced three-phase load, use RMS line quantities. For single-phase, replace √3 with 1 and use the applied voltage. φ = acos(PF) for lagging current and −acos(PF) for leading current.

Wye and Delta winding quantities

Y: V_w = V_LL / √3, I_w = I_L. Δ: V_w = V_LL, I_w = I_L / √3.

In four-wire Wye, winding voltage equals line-to-neutral voltage. The balanced Delta model has three wires and no line-to-neutral output. For single-phase, choose line-to-line or line-to-neutral according to the two supply terminals.

Optional Wye neutral vector

I_N = |I_A + I_B∠−120° + I_C∠+120°|

The neutral magnitude uses three fundamental RMS currents spaced 120° apart with the same displacement angle. The balanced power calculation is independent of these entries. Harmonic neutral loading uses the harmonic calculator.

Sinusoidal steady-state RMS with L1–L2–L3 positive sequence. The phasor arrows are line currents on an ideal phase reference. Delta winding current follows the magnitude relation shown above.