120 V line-to-neutral input

An operator can measure 120 V from L1 to N and 38 A in each line of a balanced panel.

Inputs

Supply & load
Enter the selected voltage reference. Delta uses line-to-line voltage.
Neutral study

Power triangle and phase currents

60 Hz · US customaryEdit inputs
Power triangle and phase currents at 60 Hz REAL POWER11.49kWAPPARENT13.68kVAREACTIVE7.42kVARNEUTRAL0AComplex powerφ 32.9°P · kWQ · kVARS · kVALine current phasorsYL1L2L3N sumNeutral current0 A38 A ref.

Detailed results
Real power
11.49 kW
Apparent power
13.68 kVA
Signed reactive power
7.42 kVAR
Signed phase angle
32.86°
Line-to-line voltage
207.85 V
Line-to-neutral voltage
120 V
Winding voltage
120 V
Line current
38 A
Winding current
38 A
Neutral RMS current
0 A
Single-phase apparent power at equal V & A
7.9 kVA
Single-phase real power at equal V & A
6.63 kW

Worked calculation

First multiply 120 V by √3 to recover the line voltage. Wye line current equals winding current, so use 38 A with the recovered voltage and 0.84 PF.

Line-to-line voltage
207.85 V
Winding current
38 A
Real power
11.49 kW

Values in this solution use the original example inputs.

Formulas & assumptions

Apparent, real and reactive power

S = √3 · V_LL · I_L / 1000, P = S · PF, Q = S · sin φ

For a balanced three-phase load, use RMS line quantities. For single-phase, replace √3 with 1 and use the applied voltage. φ = acos(PF) for lagging current and −acos(PF) for leading current.

Wye and Delta winding quantities

Y: V_w = V_LL / √3, I_w = I_L. Δ: V_w = V_LL, I_w = I_L / √3.

In four-wire Wye, winding voltage equals line-to-neutral voltage. The balanced Delta model has three wires and no line-to-neutral output. For single-phase, choose line-to-line or line-to-neutral according to the two supply terminals.

Optional Wye neutral vector

I_N = |I_A + I_B∠−120° + I_C∠+120°|

The neutral magnitude uses three fundamental RMS currents spaced 120° apart with the same displacement angle. The balanced power calculation is independent of these entries. Harmonic neutral loading uses the harmonic calculator.

Sinusoidal steady-state RMS with L1–L2–L3 positive sequence. The phasor arrows are line currents on an ideal phase reference. Delta winding current follows the magnitude relation shown above.