S = √3 · V_LL · I_L / 1000, P = S · PF, Q = S · sin φ
For a balanced three-phase load, use RMS line quantities. For single-phase, replace √3 with 1 and use the applied voltage. φ = acos(PF) for lagging current and −acos(PF) for leading current.
In four-wire Wye, winding voltage equals line-to-neutral voltage. The balanced Delta model has three wires and no line-to-neutral output. For single-phase, choose line-to-line or line-to-neutral according to the two supply terminals.
Optional Wye neutral vector
I_N = |I_A + I_B∠−120° + I_C∠+120°|
The neutral magnitude uses three fundamental RMS currents spaced 120° apart with the same displacement angle. The balanced power calculation is independent of these entries. Harmonic neutral loading uses the harmonic calculator.
Sinusoidal steady-state RMS with L1–L2–L3 positive sequence. The phasor arrows are line currents on an ideal phase reference. Delta winding current follows the magnitude relation shown above.
Sinusoidal steady-state RMS with L1–L2–L3 positive sequence. The phasor arrows are line currents on an ideal phase reference. Delta winding current follows the magnitude relation shown above.
Electrical safety. For engineering screening. Have a qualified, licensed electrical professional engineer (PE) review all designs. Verify compliance with the locally adopted NFPA 70 (NEC) or IEC 60364 and apply NFPA 70E workplace electrical safety practices where applicable. Complete short-circuit and protective-device coordination studies before specifying or energizing equipment.