Transformer sizing, efficiency & fault current

Size distribution transformer kVA, estimate primary and secondary full-load amps, plot efficiency, and compare finite- and infinite-bus bolted fault current.

Inputs

Nameplate & source
Use 0 for infinite bus. Enter utility fault MVA at the transformer primary.
Enter the nameplate or test ratio for peak fault estimates. Use 0 if unknown.
Use 0 to assume the utility impedance has the same angle as the transformer.
Losses & loading
Use 0 to omit minimum kVA sizing.

Transformer efficiency and fault duty

60 Hz · US customaryEdit inputs
Transformer efficiency and fault duty at 60 Hz SECONDARY FLA902.11ABOLTED FAULT15.69kAEFFICIENCY99.01%MINIMUM KVA625kVAEfficiency vs. loading100% efficiency96%6.3% load100% loadSecondary fault duty13.8 kV480 VInfinite bus15.69 kAFinite bus14.91 kANameplate loading70% load100% rated

Detailed results
Primary full-load current
31.38 A
Secondary full-load current
902.11 A
Infinite-bus symmetrical fault
15.69 kA
Finite-bus symmetrical fault
14.91 kA
Infinite-bus L–L fault on three-phase supply
13.59 kA
Finite-bus L–L fault on three-phase supply
12.91 kA
Infinite-bus asymmetrical peak
Unavailable
Finite-bus asymmetrical peak
Unavailable
Operating efficiency
99.01%
Mathematical peak efficiency load
38.55%
Peak efficiency through rated load
99.162%
Operating output power
472.5 kW
Operating load loss
3,626 W
Operating total loss
4,726 W
Minimum design capacity
625 kVA
Nameplate above minimum
125 kVA

Formulas & assumptions

Rated current and capacity

I_FLA = 1000 · kVA / (g · V), kVA_min = design kW / (PF · target load fraction)

Use g = √3 and line-to-line voltage for three-phase, or g = 1 and applied winding voltage for single-phase. Select a nameplate rating and check the reserve.

Terminal bolted fault

I_sc = I_FLA / |Z_tx + Z_src|; Z_src,pu = rated kVA / utility fault kVA

The infinite-bus case sets Z_src to zero. Enter X/R to add resistance and reactance on the same base. Without X/R, the impedance magnitudes are added assuming equal angles. For a three-phase supply with equal positive and negative sequence impedance, the L–L fault is √3/2 times the three-phase fault.

Asymmetrical peak screen

i_peak ≈ √2 · I_sc · [1.02 + 0.98 · exp(−3R/X)]

Uses the combined radial terminal impedance and nominal prefault voltage. Peak values refer to the symmetrical fault results above. They omit standard voltage and equipment correction factors and are for screening.

Losses and efficiency

η = P_out / (P_out + P₀ + x² · P_cu), x_peak = √(P₀ / P_cu)

x is load fraction relative to nameplate kVA and P_out = x · rated kVA · PF. Use consistent watts. Peak efficiency occurs when modeled load loss equals core loss.

Nominal RMS voltages, symmetric bolted fault at secondary terminals, and losses at a fixed reference temperature. Check source X/R, service voltage, impedance tolerance, downstream impedance, and contributions from motors and generators in a fault study.