Worked calculation
Use 75,000/4,160 A and 75,000/240 A without a √3 multiplier. Divide secondary current by 0.038 for the bolted terminal current at an infinite bus.
- Primary full-load current
- 18.03 A
- Secondary full-load current
- 312.5 A
- Infinite-bus symmetrical fault
- 8.22 kA
Values in this solution use the original example inputs.
Formulas & assumptions
Nominal RMS voltages, symmetric bolted fault at secondary terminals, and losses at a fixed reference temperature. Check source X/R, service voltage, impedance tolerance, downstream impedance, and contributions from motors and generators in a fault study.