Worked calculation
The square root of 1,000/4,000 gives 0.50 pu peak load. At that point the winding loss is 0.50²·4,000 = 1,000 W and total modeled losses are 2,000 W.
- Mathematical peak efficiency load
- 50%
- Operating total loss
- 2,000 W
- Operating efficiency
- 99.165%
Values in this solution use the original example inputs.
Formulas & assumptions
Nominal RMS voltages, symmetric bolted fault at secondary terminals, and losses at a fixed reference temperature. Check source X/R, service voltage, impedance tolerance, downstream impedance, and contributions from motors and generators in a fault study.