API 520 / API 526

Napier correction at high steam pressure

A high-pressure steam case uses 2,200 psia inlet and requires 55,000 lb/h of effective capacity.

Inputs

Relieving fluid and pressure
psia
psia
lb/h
Effective sizing factors

Reset restores this worked example. View results ↑

Screening result

Edit inputs ↓ Live
REQUIRED AREA 0.477 in² API LETTER G SELECTED AREA 0.503 in² UTILIZATION 94.91 % ORIFICE & VALVE Effective areaValve sectionSTEAM Orifice area headroom PASS SCREEN 0% 100% LIMIT 150%+
0.4774 in² demand / 0.503 in² limit

API letter is based on effective area. Confirm certified capacity, backpressure limits, inlet losses and the relieving scenario before selection.

Export or share
Calculation breakdown
Required effective area
0.4774 in²
API 526 letter
G
Selected API effective area
0.503 in²
Area reserve vs selected or largest letter
0.0256 in²
Required percent of reference area
94.91 %
Required equivalent circular bore
0.7796 in
Inlet to outlet differential
2,150 psid
Absolute outlet / inlet ratio
2.27 %
Gas critical ratio
—
US gas coefficient C
—
Napier high-pressure factor Kn
1.043
Effective reference mass flow
57,952.39 lb/h
Effective reference liquid flow
—
ORIGINAL PRESET

Worked calculation

A high-pressure steam case uses 2,200 psia inlet and requires 55,000 lb/h of effective capacity.

Required effective area
0.4774 in²
Napier high-pressure factor Kn
1.043
Effective reference mass flow
57,952.39 lb/h

The upper-pressure correction changes effective flow per unit area above 1,500 psia. Compare the resulting effective area and letter.

Calculation basis

  1. Gas at critical flow

    Check the absolute outlet-to-inlet ratio against the critical ratio. Use relieving temperature in Rankine in the customary equation. P₁ represents the actual valve inlet under relief, including the applicable overpressure and inlet losses.

    W = C·Kd·P₁·Kb·Kc·A·√(M/(T·Z)) · C = 520√[k(2/(k+1))^((k+1)/(k−1))]

  2. Steam and liquid

    Use Ksh = 1 for saturated steam. The Napier correction Kn applies above 1,500 psia through 3,200 psia. This screen assumes low outlet pressure for steam. The liquid equation uses US gal/min and verified correction factors.

    Wsteam = 51.5·P₁·A·Kd·Kb·Kc·Kn·Ksh · Qliquid = 38·Kd·Kw·Kc·Kv·A·√(ΔP/G)

  3. API effective letter

    Choose the smallest D through T area meeting the computed requirement. If the demand exceeds T, compare against T as a reference and flag the case for engineering review.

    Utilization = 100 × Arequired / Areference

Use an independently established relief load and actual relieving conditions. Verify API 520 method applicability, allowable backpressure and installation, flashing or two-phase flow, valve certification, and manufacturer-rated capacity.

Sources and verification scope ↗