API 520 / API 526

Low-molecular-weight gas relief

A critical low-molecular-weight gas case uses M = 4.0, k = 1.66, Z = 1.03 and a verified backpressure factor of 0.92.

Inputs

Relieving fluid and pressure
psia
psia
lb/h
°F
lb/lbmol
Effective sizing factors

Reset restores this worked example. View results ↑

Screening result

Edit inputs ↓ Live
REQUIRED AREA 1.018 in² API LETTER J SELECTED AREA 1.287 in² UTILIZATION 79.13 % ORIFICE & VALVE Effective areaValve sectionCRITICAL GAS Orifice area headroom PASS SCREEN 0% 100% LIMIT 150%+
1.0184 in² demand / 1.287 in² limit

API letter is based on effective area. Confirm certified capacity, backpressure limits, inlet losses and the relieving scenario before selection.

Export or share
Calculation breakdown
Required effective area
1.0184 in²
API 526 letter
J
Selected API effective area
1.287 in²
Area reserve vs selected or largest letter
0.2686 in²
Required percent of reference area
79.13 %
Required equivalent circular bore
1.1387 in
Inlet to outlet differential
365 psid
Absolute outlet / inlet ratio
17.05 %
Gas critical ratio
48.81 %
US gas coefficient C
377.1183
Napier high-pressure factor Kn
—
Effective reference mass flow
15,164.65 lb/h
Effective reference liquid flow
—
ORIGINAL PRESET

Worked calculation

A critical low-molecular-weight gas case uses M = 4.0, k = 1.66, Z = 1.03 and a verified backpressure factor of 0.92.

Required effective area
1.0184 in²
API 526 letter
J
Gas critical ratio
48.81 %

Low molecular weight reduces mass flow per unit area at otherwise comparable conditions. Check the sonic ratio and area utilization.

Calculation basis

  1. Gas at critical flow

    Check the absolute outlet-to-inlet ratio against the critical ratio. Use relieving temperature in Rankine in the customary equation. P₁ represents the actual valve inlet under relief, including the applicable overpressure and inlet losses.

    W = C·Kd·P₁·Kb·Kc·A·√(M/(T·Z)) · C = 520√[k(2/(k+1))^((k+1)/(k−1))]

  2. Steam and liquid

    Use Ksh = 1 for saturated steam. The Napier correction Kn applies above 1,500 psia through 3,200 psia. This screen assumes low outlet pressure for steam. The liquid equation uses US gal/min and verified correction factors.

    Wsteam = 51.5·P₁·A·Kd·Kb·Kc·Kn·Ksh · Qliquid = 38·Kd·Kw·Kc·Kv·A·√(ΔP/G)

  3. API effective letter

    Choose the smallest D through T area meeting the computed requirement. If the demand exceeds T, compare against T as a reference and flag the case for engineering review.

    Utilization = 100 × Arequired / Areference

Use an independently established relief load and actual relieving conditions. Verify API 520 method applicability, allowable backpressure and installation, flashing or two-phase flow, valve certification, and manufacturer-rated capacity.

Sources and verification scope ↗