API 520 / API 526
Saturated steam relief at 300 psia
A vessel requires 12,000 lb/h saturated steam relief at 300 psia with low total outlet pressure.
Inputs
Reset restores this worked example. View results ↑
Screening result
Edit inputs ↓ LiveAPI letter is based on effective area. Confirm certified capacity, backpressure limits, inlet losses and the relieving scenario before selection.
Calculation breakdown
- Required effective area
- 0.7966 in²
- API 526 letter
- J
- Selected API effective area
- 1.287 in²
- Area reserve vs selected or largest letter
- 0.4904 in²
- Required percent of reference area
- 61.9 %
- Required equivalent circular bore
- 1.0071 in
- Inlet to outlet differential
- 278 psid
- Absolute outlet / inlet ratio
- 7.33 %
- Gas critical ratio
- —
- US gas coefficient C
- —
- Napier high-pressure factor Kn
- 1
- Effective reference mass flow
- 19,387.05 lb/h
- Effective reference liquid flow
- —
Worked calculation
A vessel requires 12,000 lb/h saturated steam relief at 300 psia with low total outlet pressure.
- Required effective area
- 0.7966 in²
- API 526 letter
- J
- Napier high-pressure factor Kn
- 1
Saturated steam uses a steam factor of one. The relieving pressure stays within the base Napier range for this case.
Calculation basis
Gas at critical flow
Check the absolute outlet-to-inlet ratio against the critical ratio. Use relieving temperature in Rankine in the customary equation. P₁ represents the actual valve inlet under relief, including the applicable overpressure and inlet losses.
W = C·Kd·P₁·Kb·Kc·A·√(M/(T·Z)) · C = 520√[k(2/(k+1))^((k+1)/(k−1))]Steam and liquid
Use Ksh = 1 for saturated steam. The Napier correction Kn applies above 1,500 psia through 3,200 psia. This screen assumes low outlet pressure for steam. The liquid equation uses US gal/min and verified correction factors.
Wsteam = 51.5·P₁·A·Kd·Kb·Kc·Kn·Ksh · Qliquid = 38·Kd·Kw·Kc·Kv·A·√(ΔP/G)API effective letter
Choose the smallest D through T area meeting the computed requirement. If the demand exceeds T, compare against T as a reference and flag the case for engineering review.
Utilization = 100 × Arequired / Areference
Use an independently established relief load and actual relieving conditions. Verify API 520 method applicability, allowable backpressure and installation, flashing or two-phase flow, valve certification, and manufacturer-rated capacity.