API 520 / API 526

Saturated steam relief at 300 psia

A vessel requires 12,000 lb/h saturated steam relief at 300 psia with low total outlet pressure.

Inputs

Relieving fluid and pressure
psia
psia
lb/h
Effective sizing factors

Reset restores this worked example. View results ↑

Screening result

Edit inputs ↓ Live
REQUIRED AREA 0.797 in² API LETTER J SELECTED AREA 1.287 in² UTILIZATION 61.9 % ORIFICE & VALVE Effective areaValve sectionSTEAM Orifice area headroom PASS SCREEN 0% 100% LIMIT 150%+
0.7966 in² demand / 1.287 in² limit

API letter is based on effective area. Confirm certified capacity, backpressure limits, inlet losses and the relieving scenario before selection.

Export or share
Calculation breakdown
Required effective area
0.7966 in²
API 526 letter
J
Selected API effective area
1.287 in²
Area reserve vs selected or largest letter
0.4904 in²
Required percent of reference area
61.9 %
Required equivalent circular bore
1.0071 in
Inlet to outlet differential
278 psid
Absolute outlet / inlet ratio
7.33 %
Gas critical ratio
—
US gas coefficient C
—
Napier high-pressure factor Kn
1
Effective reference mass flow
19,387.05 lb/h
Effective reference liquid flow
—
ORIGINAL PRESET

Worked calculation

A vessel requires 12,000 lb/h saturated steam relief at 300 psia with low total outlet pressure.

Required effective area
0.7966 in²
API 526 letter
J
Napier high-pressure factor Kn
1

Saturated steam uses a steam factor of one. The relieving pressure stays within the base Napier range for this case.

Calculation basis

  1. Gas at critical flow

    Check the absolute outlet-to-inlet ratio against the critical ratio. Use relieving temperature in Rankine in the customary equation. P₁ represents the actual valve inlet under relief, including the applicable overpressure and inlet losses.

    W = C·Kd·P₁·Kb·Kc·A·√(M/(T·Z)) · C = 520√[k(2/(k+1))^((k+1)/(k−1))]

  2. Steam and liquid

    Use Ksh = 1 for saturated steam. The Napier correction Kn applies above 1,500 psia through 3,200 psia. This screen assumes low outlet pressure for steam. The liquid equation uses US gal/min and verified correction factors.

    Wsteam = 51.5·P₁·A·Kd·Kb·Kc·Kn·Ksh · Qliquid = 38·Kd·Kw·Kc·Kv·A·√(ΔP/G)

  3. API effective letter

    Choose the smallest D through T area meeting the computed requirement. If the demand exceeds T, compare against T as a reference and flag the case for engineering review.

    Utilization = 100 × Arequired / Areference

Use an independently established relief load and actual relieving conditions. Verify API 520 method applicability, allowable backpressure and installation, flashing or two-phase flow, valve certification, and manufacturer-rated capacity.

Sources and verification scope ↗