Joukowsky / elastic pipe
Slow closure on a ductile-iron line
A ductile-iron distribution line uses a motorized valve with 3.5 seconds of effective closure time.
Inputs
Results
Edit inputs- Wave speed
- 1,300.3m/s
- Critical time
- 0.338s
- Surge rise
- 213.3kPa
- Peak pressure
- 6.4bar g
Slow closure gives a peak at or below the rating. Transient reflections and vacuum require separate review.
Joukowsky surge envelope
All calculated values
| Elastic wave speed | 1,300.3 m/s |
|---|---|
| Round-trip time | 0.3384 s |
| Closure regime | Slow |
| Instantaneous Joukowsky rise | 2,206.16 kPa |
| Closure-adjusted surge rise | 213.29 kPa |
| Peak line pressure | 6.43 bar g |
| Remaining rating margin | 956.71 kPa |
| Rating used | 40.2 % |
| Nominal wall modulus E | 165 GPa |
| Diameter-to-wall ratio | 22.8 |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Find the elastic wave speed1,300.3 m/s
- Compare closure with round-trip time0.3384 s
- Add surge to line pressure6.43 bar g
The screen attenuates the sudden pressure rise because closure exceeds a round trip. Actual closure depends on the valve characteristic.
Model and limits
The elastic wall model represents one full liquid line between the valve and a reflecting boundary. Enter the effective closure time and the velocity reduction across the event. Use a consistent gauge pressure basis for initial pressure and rating.
Instantaneous closure uses the full Joukowsky rise. The slow-closure factor is a linear-closure approximation. Preset pipe moduli are nominal short-term values. Check restraint, viscoelasticity, nonlinear closure, branches, reflected waves and vapor-column separation with transient analysis. Enter the temperature-corrected rating of the weakest relevant component.
View equations and references