Joukowsky / elastic pipe
HDPE line with extended closure
An HDPE transfer line uses an eight-second effective shutoff interval.
Inputs
Results
Edit inputs- Wave speed
- 308.5m/s
- Critical time
- 3.565s
- Surge rise
- 178.4kPa
- Peak pressure
- 6bar g
Slow closure gives a peak at or below the rating. Transient reflections and vacuum require separate review.
Joukowsky surge envelope
All calculated values
| Elastic wave speed | 308.5 m/s |
|---|---|
| Round-trip time | 3.5652 s |
| Closure regime | Slow |
| Instantaneous Joukowsky rise | 400.29 kPa |
| Closure-adjusted surge rise | 178.39 kPa |
| Peak line pressure | 5.98 bar g |
| Remaining rating margin | 401.61 kPa |
| Rating used | 59.8 % |
| Nominal wall modulus E | 1 GPa |
| Diameter-to-wall ratio | 10.1 |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Find the elastic wave speed308.5 m/s
- Compare closure with round-trip time3.5652 s
- Add surge to line pressure5.98 bar g
The modulus preset is a short-term value. A viscoelastic transient model can change the result for long plastic runs.
Model and limits
The elastic wall model represents one full liquid line between the valve and a reflecting boundary. Enter the effective closure time and the velocity reduction across the event. Use a consistent gauge pressure basis for initial pressure and rating.
Instantaneous closure uses the full Joukowsky rise. The slow-closure factor is a linear-closure approximation. Preset pipe moduli are nominal short-term values. Check restraint, viscoelasticity, nonlinear closure, branches, reflected waves and vapor-column separation with transient analysis. Enter the temperature-corrected rating of the weakest relevant component.
View equations and references