Joukowsky / elastic pipe

Partial closure with a 2 ft/s velocity change

A control valve throttles rapidly from one flowing condition to another without reaching its seat.

Inputs

Liquid and pipe
Closure and pressure
Wave speed
4,377.5ft/s
Critical time
0.16s
Surge rise
117.7psi
Peak pressure
222.7psig
Peak within entered rating

Rapid closure gives a peak at or below the rating. Transient reflections and vacuum require separate review.

Joukowsky surge envelope

Joukowsky surge envelopePeak pressure versus closure time on a compressed time scale. The dashed vertical line marks the round-trip time.0164327psig0 sCLOSURE TIME0.6 sPEAK ENVELOPEPIPE RATINGPEAK222.7 psigRATING300 psigMARGIN77.3 psi
Peak pressure versus closure time on a compressed time scale. The dashed vertical line marks the round-trip time.

All calculated values
Elastic wave speed4,377.5 ft/s
Round-trip time0.1599 s
Closure regimeRapid
Instantaneous Joukowsky rise117.73 psi
Closure-adjusted surge rise117.73 psi
Peak line pressure222.73 psig
Remaining rating margin77.27 psi
Rating used74.2 %
Nominal wall modulus E29.01 Mpsi
Diameter-to-wall ratio21.7

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Find the elastic wave speed4,377.5 ft/s
  2. Compare closure with round-trip time0.1599 s
  3. Add surge to line pressure222.73 psig

Use the change in velocity rather than the full initial velocity. The screen adds the corresponding positive rise to operating pressure.

Model and limits

The elastic wall model represents one full liquid line between the valve and a reflecting boundary. Enter the effective closure time and the velocity reduction across the event. Use a consistent gauge pressure basis for initial pressure and rating.

Instantaneous closure uses the full Joukowsky rise. The slow-closure factor is a linear-closure approximation. Preset pipe moduli are nominal short-term values. Check restraint, viscoelasticity, nonlinear closure, branches, reflected waves and vapor-column separation with transient analysis. Enter the temperature-corrected rating of the weakest relevant component.

View equations and references

Worked examples