Joukowsky / elastic pipe
PVC line wave-speed comparison
A flexible PVC line operates at modest static pressure with rapid isolation.
Inputs
Results
Edit inputs- Wave speed
- 401m/s
- Critical time
- 0.499s
- Surge rise
- 600.2kPa
- Peak pressure
- 9.5bar g
Rapid closure gives a positive surge above the entered pressure rating.
Joukowsky surge envelope
All calculated values
| Elastic wave speed | 401 m/s |
|---|---|
| Round-trip time | 0.4988 s |
| Closure regime | Rapid |
| Instantaneous Joukowsky rise | 600.25 kPa |
| Closure-adjusted surge rise | 600.25 kPa |
| Peak line pressure | 9.5 bar g |
| Remaining rating margin | -50.25 kPa |
| Rating used | 105.6 % |
| Nominal wall modulus E | 3 GPa |
| Diameter-to-wall ratio | 17.3 |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Find the elastic wave speed401 m/s
- Compare closure with round-trip time0.4988 s
- Add surge to line pressure9.5 bar g
The compliant wall reduces wave speed. Correct the allowable pressure and elastic properties for material grade and temperature.
Model and limits
The elastic wall model represents one full liquid line between the valve and a reflecting boundary. Enter the effective closure time and the velocity reduction across the event. Use a consistent gauge pressure basis for initial pressure and rating.
Instantaneous closure uses the full Joukowsky rise. The slow-closure factor is a linear-closure approximation. Preset pipe moduli are nominal short-term values. Check restraint, viscoelasticity, nonlinear closure, branches, reflected waves and vapor-column separation with transient analysis. Enter the temperature-corrected rating of the weakest relevant component.
View equations and references