ACI 318-19 §16.3 / §21.2 / §22.8

Compression above the confined bearing limit

A large, fully confined support still needs a transfer path for load above the bearing ceiling.

Edit inputs ↓

Inputs

Editable example

Contact & support
Interface steel
φBn 636.48kip
Area A₂ 2,304in²
Confinement 2 
Excess Pu 163.52kip
AnatomyDiagrammatic scale
Parameter-linked bearing drawing. Diagrammatic scale. SUPPORT SECTIONPROJECTED PLAN1V : 2H projectionA₁ 144 in²A₂ 2,304 in²× 2

Screening

Limit exceeded
Bearing utilization125.7%
Confined bearing25.7% over the threshold
  • Projection geometryA₂ fits within the 1V:2H envelope
    Within limit
  • Concrete bearing strengthExcess load needs a separate transfer design
    Outside limit
  • Interface reinforcementDowel or continuous steel area ≥ 0.005Ag
    Within limit

Concentric compression on a rectangular support with uniform depth. Check the loaded member side, eccentricity, punching, dowel development, shear friction and actual reinforcement load transfer separately.

Calculation readout
QuantityValue
Design bearing φBn636.48 kip
Supporting area A₂ used2,304 in²
Confinement multiplier2
Demand beyond concrete bearing163.52 kip
Loaded area A₁144 in²
Maximum projected area A₂2,304 in²
Permitted side projection18 in
Nominal bearing Bn979.2 kip
Supported gross area Ag144 in²
Minimum interface steel0.72 in²
Provided interface steel2.48 in²

Original example

Worked solution

Default calculator ↗

Starting inputs

Support width
48 in
Support length
48 in
Available projection depth
12 in
Factored compression Pu
800 kip
Dowel count (0: none)
8

Calculated result

Design bearing φBn
636.48 kip
Supporting area A₂ used
2,304 in²
Confinement multiplier
2
Demand beyond concrete bearing
163.52 kip

Separate the bearing contribution and excess compression. Meeting minimum dowel area does not establish the dowels’ transfer capacity.

Preset screening · Confined bearing · Limit exceeded

How the check works

Code basis ↗
  1. Take A₁ as loaded width × length. At 1V:2H the uniform side projection is limited by 2 × depth and the nearest support edge. The resulting footprint bounds A₂.
  2. Use φBn = 0.65 × 0.85f′c A₁ × min(√(A₂/A₁), 2). Confinement requires support beyond all loaded edges. Report any Pu above φBn as force requiring a separately designed transfer path.
  3. For a cast-in-place column or pedestal to foundation, compare the provided interface steel with 0.005 times supported gross area. A₁ is the default when it represents the gross area of the supported member.