ACI 318-19 §16.3 / §21.2 / §22.8

Pedestal interface with no crossing bars

Bearing stress is within the concrete limit, but no interface reinforcement is specified.

Edit inputs ↓

Inputs

Editable example

Contact & support
Interface steel
φBn 636.48kip
Area A₂ 576in²
Confinement 2 
Excess Pu 0kip
AnatomyDiagrammatic scale
Parameter-linked bearing drawing. Diagrammatic scale. SUPPORT SECTIONPROJECTED PLAN1V : 2H projectionA₁ 144 in²A₂ 576 in²× 2

Screening

Limit exceeded
Bearing utilization44%
Confined bearing56% below the threshold
  • Projection geometryA₂ fits within the 1V:2H envelope
    Within limit
  • Concrete bearing strengthPu ≤ φBn
    Within limit
  • Interface reinforcementDowel or continuous steel area ≥ 0.005Ag
    Outside limit

Concentric compression on a rectangular support with uniform depth. Check the loaded member side, eccentricity, punching, dowel development, shear friction and actual reinforcement load transfer separately.

Calculation readout
QuantityValue
Design bearing φBn636.48 kip
Supporting area A₂ used576 in²
Confinement multiplier2
Demand beyond concrete bearing0 kip
Loaded area A₁144 in²
Maximum projected area A₂576 in²
Permitted side projection6 in
Nominal bearing Bn979.2 kip
Supported gross area Ag144 in²
Minimum interface steel0.72 in²
Provided interface steel0 in²

Original example

Worked solution

Default calculator ↗

Starting inputs

Factored compression Pu
280 kip
Dowel count (0: none)
0

Calculated result

Design bearing φBn
636.48 kip
Supporting area A₂ used
576 in²
Confinement multiplier
2
Demand beyond concrete bearing
0 kip

Check the minimum crossing steel against the supported gross area separately from bearing.

Preset screening · Confined bearing · Limit exceeded

How the check works

Code basis ↗
  1. Take A₁ as loaded width × length. At 1V:2H the uniform side projection is limited by 2 × depth and the nearest support edge. The resulting footprint bounds A₂.
  2. Use φBn = 0.65 × 0.85f′c A₁ × min(√(A₂/A₁), 2). Confinement requires support beyond all loaded edges. Report any Pu above φBn as force requiring a separately designed transfer path.
  3. For a cast-in-place column or pedestal to foundation, compare the provided interface steel with 0.005 times supported gross area. A₁ is the default when it represents the gross area of the supported member.