RoomAcousticLab · Calculation record
Noise barrier example
Low-frequency plant screen
A barrier that blocks line of sight can still provide modest attenuation at low frequency. Test the 63 Hz response for a long-wavelength source.
Inputs
- Insertion loss
- 6.3dB
- Fresnel N
- 0.065
- Path diff.
- 0.178m
- Tip clearance
- 1.47m
Barrier cross-section & ray paths
Illustrative scaleInsertion-loss target shortfall
LimitThe modelled value falls on the wrong side of the entered target.
≥ 2 dB reserveGrazing / reviewBelow target
Input snapshot
- Source height
- 1 m
- Receiver height
- 1.7 m
- Barrier height
- 2.7 m
- Source to barrier
- 9 m
- Barrier to receiver
- 18 m
- Barrier type
- Thin wall · 20 dB cap
- Band frequency
- 63 Hz
- Air temperature
- 20 °C
- Target insertion loss
- 9 dB
Calculation breakdown
- Source to tip A
- 9.159 m
- Tip to receiver B
- 18.028 m
- Direct path d
- 27.009 m
- Wavelength λ
- 5.448 m
- Diffraction zone
- Shadow
- Uncapped estimate
- 6.34 dB
- Practical screening cap
- 20 dB
- Target margin
- -2.66 dB
The section assumes a continuous, acoustically opaque barrier with one dominant top edge. Finite length, ground effects, reflection and sound through the barrier can change the actual insertion loss.