Noise barrier example

Low-frequency plant screen

A barrier that blocks line of sight can still provide modest attenuation at low frequency. Test the 63 Hz response for a long-wavelength source.

Inputs

Barrier section
Frequency & target
Insertion loss
6.3dB
Fresnel N
0.065
Path diff.
0.178m
Tip clearance
1.47m

Barrier cross-section & ray paths

Illustrative scale
Noise barrier ray geometryThe indigo sight line joins source and receiver and the teal ray follows the top of the wall or berm. The two horizontal distances and all three heights update with the inputs.SOURCEWALL TIPRECEIVER1 m2.7 m1.7 md₁ 9 md₂ 18 m
DiffractedSight lineBarrier

Insertion-loss target shortfall

Limit

The modelled value falls on the wrong side of the entered target.

≥ 2 dB reserveGrazing / reviewBelow target

Calculation breakdown

Source to tip A
9.159 m
Tip to receiver B
18.028 m
Direct path d
27.009 m
Wavelength λ
5.448 m
Diffraction zone
Shadow
Uncapped estimate
6.34 dB
Practical screening cap
20 dB
Target margin
-2.66 dB