RoomAcousticLab · Calculation record
Partition transmission example
Office door in a rated wall
A lower-performing door occupies a small fraction of a wall. Compare the resulting band transmission loss with the solid partition and the selected target.
Inputs
- Composite TL
- 39dB
- Wall penalty
- 12.98dB
- Open gap
- 0%
- Target margin
- -2.98dB
Partition elevation & leak response
Illustrative scaleTransmission target shortfall
LimitThe modelled value falls on the wrong side of the entered target.
≥ 3 dB reserve0–3 dB reserveBelow target
Input snapshot
- Total area
- 20 m²
- Solid wall TL
- 52 dB
- Target TL
- 42 dB
- Weak element
- Door
- Element area
- 1.9 m²
- Element TL
- 29 dB
- Open gap area
- 0 m²
Calculation breakdown
- Solid wall area
- 18.1 m²
- Weak element share
- 9.5%
- Transmission loss with the gap sealed
- 39.02 dB
- Target band TL
- 42 dB
| Open area | Composite TL | Wall penalty |
|---|---|---|
| 0% | 39.02 dB | 12.98 dB |
| 0.001% | 38.69 dB | 13.313 dB |
| 0.01% | 36.47 dB | 15.528 dB |
| 0.1% | 29.49 dB | 22.513 dB |
| 1% | 19.95 dB | 32.054 dB |
| 5% | 13 dB | 39.001 dB |
Matched single-number ratings can provide a rough comparison. A rated composite STC requires a frequency-band TL curve and the ASTM E413 fitting procedure. Treat indirect structure-borne and duct transmission as separate paths.