RoomAcousticLab · Calculation record
Partition transmission example
Service room transfer louver
A transfer louver is a low-TL path through a large utility room wall. Estimate the isolation loss when the louver is left untreated.
Inputs
- Composite TL
- 28.3dB
- Wall penalty
- 27.68dB
- Open gap
- 0%
- Target margin
- -16.68dB
Partition elevation & leak response
Illustrative scaleTransmission target shortfall
LimitThe modelled value falls on the wrong side of the entered target.
≥ 3 dB reserve0–3 dB reserveBelow target
Input snapshot
- Total area
- 34 m²
- Solid wall TL
- 56 dB
- Target TL
- 45 dB
- Weak element
- Louver
- Element area
- 0.5 m²
- Element TL
- 10 dB
- Open gap area
- 0 m²
Calculation breakdown
- Solid wall area
- 33.5 m²
- Weak element share
- 1.471%
- Transmission loss with the gap sealed
- 28.32 dB
- Target band TL
- 45 dB
| Open area | Composite TL | Wall penalty |
|---|---|---|
| 0% | 28.32 dB | 27.682 dB |
| 0.001% | 28.29 dB | 27.712 dB |
| 0.01% | 28.03 dB | 27.967 dB |
| 0.1% | 26.07 dB | 29.932 dB |
| 1% | 19.4 dB | 36.597 dB |
| 5% | 12.88 dB | 43.116 dB |
Matched single-number ratings can provide a rough comparison. A rated composite STC requires a frequency-band TL curve and the ASTM E413 fitting procedure. Treat indirect structure-borne and duct transmission as separate paths.