RoomAcousticLab · Calculation record
Partition transmission example
Sealed archive wall
A homogeneous wall has no separate door or gap in the tested area. Its composite result should match the entered wall TL exactly.
Inputs
- Composite TL
- 49dB
- Wall penalty
- 0dB
- Open gap
- 0%
- Target margin
- 6dB
Partition elevation & leak response
Illustrative scaleTransmission target cleared
PassThe estimate clears the entered target by at least 3 dB.
≥ 3 dB reserve0–3 dB reserveBelow target
Input snapshot
- Total area
- 18 m²
- Solid wall TL
- 49 dB
- Target TL
- 43 dB
- Weak element
- Door
- Element area
- 0 m²
- Element TL
- 35 dB
- Open gap area
- 0 m²
Calculation breakdown
- Solid wall area
- 18 m²
- Weak element share
- 0%
- Transmission loss with the gap sealed
- 49 dB
- Target band TL
- 43 dB
| Open area | Composite TL | Wall penalty |
|---|---|---|
| 0% | 49 dB | 0 dB |
| 0.001% | 46.46 dB | 2.539 dB |
| 0.01% | 39.49 dB | 9.515 dB |
| 0.1% | 29.95 dB | 19.054 dB |
| 1% | 19.99 dB | 29.005 dB |
| 5% | 13.01 dB | 35.991 dB |
Matched single-number ratings can provide a rough comparison. A rated composite STC requires a frequency-band TL curve and the ASTM E413 fitting procedure. Treat indirect structure-borne and duct transmission as separate paths.