Worked example · Simple-span statics · ASCE 7-16 §12.10 context

Distribution across three wall gaps

Three door openings lie on one collector line, separated by short resisting piers. The line-load screen tracks each transfer independently.

Calculation sheet
Export

Inputs

Diaphragm loading and geometry
plf
ft
ft
Collector openings

Measure along the supporting wall from one end. A zero gap length removes that opening.

Wall gap 1
ft
ft
Wall gap 2
ft
ft
Wall gap 3
ft
ft
UNIT SHEAR
694.4plf
CHORD FORCE
19.443kip
PEAK DRAG
8.333kip
ASPECT L/B
2.24
Proportion: At or below 3:1

Compare this geometry with the limits and fastening details for the specific diaphragm assembly.

Diaphragm plan & chordsCompression chordTension chordL 112 ftB 50 ftShear and collector profileSigned span shear±34.72 kipCollector drag at gaps8.33 kip050 ft
Plan and load diagrams for a uniform span. The collector line plots the drag that builds across each opening.

Calculation detail

Reaction at each wall
34.72 kip
Maximum diaphragm moment
972.16 kip·ft
Tension chord
19.443 kip
Compression chord
19.443 kip
Collector openings
GapStart (ft)End (ft)Drag (kip)
12116.2496
217298.3328
335467.6384

How the calculation works

Read this example

The drag profile resets at each pier in this model. A continuous collector can require an explicit axial-force analysis.

Preset result: UNIT SHEAR 694.4 plf.

Find the support and chord forces

Uniform line load gives V = wL/2 and M = wL²/8. The peak diaphragm unit shear is V/B. Treat the tension and compression chords as a force couple separated by B, giving M/B in each chord.

Follow the shear across wall openings

A gap interrupts the uniform transfer line. The transferred drag across an isolated opening is unit shear times its length. The profile resets at the next pier in this model.

Read the aspect ratio as a screen

L/B is compared with 3:1 and 4:1 for early layout review. The actual permitted ratio depends on the chosen system and applicable material standard.

Design scope

Provide the governing design line load. Check collector continuity, overstrength, pier capacity, material limits, flexible or rigid distribution, and force transfer around openings separately.

Source references
  • ASCE/SEI 7-16 standardhttps://ascelibrary.org/doi/book/10.1061/9780784414248
  • FEMA P-1051 design exampleshttps://www.fema.gov/sites/default/files/2020-07/fema_nehrp-seismic-provisions-examples_p-1051_20160701.pdf

More diaphragm, chords & collectors examples