Worked example · Simple-span statics · ASCE 7-16 §12.10 context

Timber warehouse with door openings

A uniform roof diaphragm spans between two wall lines. Two unequal doors interrupt one of the collector transfer lines.

Calculation sheet
Export

Inputs

Diaphragm loading and geometry
plf
ft
ft
Collector openings

Measure along the supporting wall from one end. A zero gap length removes that opening.

Wall gap 1
ft
ft
Wall gap 2
ft
ft
Wall gap 3
ft
ft
UNIT SHEAR
697.895plf
CHORD FORCE
17.796kip
PEAK DRAG
7.677kip
ASPECT L/B
2.68
Proportion: At or below 3:1

Compare this geometry with the limits and fastening details for the specific diaphragm assembly.

Diaphragm plan & chordsCompression chordTension chordL 102 ftB 38 ftShear and collector profileSigned span shear±26.52 kipCollector drag at gaps7.68 kip038 ft
Plan and load diagrams for a uniform span. The collector line plots the drag that builds across each opening.

Calculation detail

Reaction at each wall
26.52 kip
Maximum diaphragm moment
676.26 kip·ft
Tension chord
17.796 kip
Compression chord
17.796 kip
Collector openings
GapStart (ft)End (ft)Drag (kip)
14157.6768
222305.5832

How the calculation works

Read this example

The wider opening accumulates more drag in this uniform unit shear model. Verify each pier can take the transferred force.

Preset result: UNIT SHEAR 697.895 plf.

Find the support and chord forces

Uniform line load gives V = wL/2 and M = wL²/8. The peak diaphragm unit shear is V/B. Treat the tension and compression chords as a force couple separated by B, giving M/B in each chord.

Follow the shear across wall openings

A gap interrupts the uniform transfer line. The transferred drag across an isolated opening is unit shear times its length. The profile resets at the next pier in this model.

Read the aspect ratio as a screen

L/B is compared with 3:1 and 4:1 for early layout review. The actual permitted ratio depends on the chosen system and applicable material standard.

Design scope

Provide the governing design line load. Check collector continuity, overstrength, pier capacity, material limits, flexible or rigid distribution, and force transfer around openings separately.

Source references
  • ASCE/SEI 7-16 standardhttps://ascelibrary.org/doi/book/10.1061/9780784414248
  • FEMA P-1051 design exampleshttps://www.fema.gov/sites/default/files/2020-07/fema_nehrp-seismic-provisions-examples_p-1051_20160701.pdf

More diaphragm, chords & collectors examples