Convert conductivity to feed TDS

A temperature-compensated feedwater conductivity result is 600 µS/cm. The site conversion factor is 0.58 ppm per µS/cm.

Inputs

lb/hr
psig
µS/cm
ppm/(µS/cm)
Use the site-specific relationship at the sample reference temperature.
%
°F
psig
%
%
%
h/yr
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
Drum solids and heat-recovery balance
Drum solids and heat-recovery balanceBLOWDOWN 11.04 %. CYCLES 10.057 ×. BD FLOW 1,324.9 lb/hr. FUEL SAVINGS 19.97K USD/yrBLOWDOWN11.04%CYCLES10.057×BD FLOW1,324.9lb/hrFUEL SAVINGS19.97KUSD/yrBOILER DRUM3,500 ppm targetFEEDWATER348 ppm inLIVE STEAMFLASH + HX73.97% recoveredBLOWDOWNRecovered / gross blowdown heat73.97%0%Annual sensible and latent heat100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

  • Blowdown exceeds 10% of steam production. Review feedwater quality and treatment.
Blowdown / steam production
11.04%
Blowdown flow
1,324.9lb/hr
TDS cycles of concentration
10.057×
Fresh make-up flow
6,724.9lb/hr
Total boiler feedwater
13,324.9lb/hr
Effective feedwater TDS
348ppm
Drum TDS target
3,500ppm
ABMA screening value
3,500ppm
Gross annual blowdown heat
2,604.5MMBtu/yr
Generated flash steam with recovery
197.4lb/hr
Usable flash heat
170,666.48Btu/h
Liquid HX heat
125,724.01Btu/h
Annual heat recovered
1,926.5MMBtu/yr
Annual unrecovered heat
677.9MMBtu/yr
Annual fuel energy avoided
2,349.4MMBtu/yr
Annual fuel savings
19,970USD/yr

Check the original case

Effective feedwater TDS is 348 ppm. Confirm that higher feed concentration raises blowdown.

  • Blowdown / steam production11.04 %
  • TDS cycles of concentration10.057 ×
  • Blowdown flow1,324.9 lb/hr
  • Annual fuel savings19,970 USD/yr

Formulas and assumptions

Steady drum solids

BD/S = F/(B − F); cycles = B/F

F is the effective feedwater TDS, B is the drum target and S is dry steam production. Conductivity is multiplied by an editable site factor. Zero feed TDS gives zero calculated continuous blowdown and unlimited theoretical cycles.

Water balance and screening bands

Feed = S + BD; make-up = feed − returned condensate

ABMA screening values are 3,500 ppm through 300 psig, 3,000 ppm above 300 through 450 psig, and 2,500 ppm above 450 through 600 psig. Use the verified OEM or site target when it is more restrictive.

Flash and heat exchanger

f = (h_f,boiler − h_f,receiver)/h_fg,receiver; Q_BD = BD·(h_f,boiler − h_makeup)

Usable vapor yields flash latent heat. The exchanger recovers an entered fraction of the remaining liquid sensible heat relative to make-up. Divide recovered heat by boiler efficiency to estimate fuel avoided.

Worked examples

Open a case to edit its inputs.