500 psig drum with a site TDS limit

The site sets a 1,800 ppm drum target on a 500 psig boiler. Size the continuous discharge for a 110 ppm feed.

Inputs

lb/hr
psig
ppm
ppm
%
°F
psig
%
%
%
h/yr
Currency labels your tariff and savings. Enter local prices.
USD/MMBtu
Drum solids and heat-recovery balance
Drum solids and heat-recovery balanceBLOWDOWN 6.51 %. CYCLES 16.364 ×. BD FLOW 1,366.9 lb/hr. FUEL SAVINGS 28.06K USD/yrBLOWDOWN6.51%CYCLES16.364×BD FLOW1,366.9lb/hrFUEL SAVINGS28.06KUSD/yrBOILER DRUM1,800 ppm targetFEEDWATER110 ppm inLIVE STEAMFLASH + HX73.1% recoveredBLOWDOWNRecovered / gross blowdown heat73.1%0%Annual sensible and latent heat100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Blowdown / steam production
6.51%
Blowdown flow
1,366.9lb/hr
TDS cycles of concentration
16.364×
Fresh make-up flow
7,666.9lb/hr
Total boiler feedwater
22,366.9lb/hr
Effective feedwater TDS
110ppm
Drum TDS target
1,800ppm
ABMA screening value
2,500ppm
Gross annual blowdown heat
3,703.5MMBtu/yr
Generated flash steam with recovery
328lb/hr
Usable flash heat
277,349.81Btu/h
Liquid HX heat
139,177.61Btu/h
Annual heat recovered
2,707.4MMBtu/yr
Annual unrecovered heat
996.1MMBtu/yr
Annual fuel energy avoided
3,301.7MMBtu/yr
Annual fuel savings
28,065USD/yr

Check the original case

Compare the site target with the 2,500 ppm screening band and check the corresponding blowdown flows.

  • Blowdown / steam production6.51 %
  • TDS cycles of concentration16.364 ×
  • Blowdown flow1,366.9 lb/hr
  • Annual fuel savings28,065 USD/yr

Formulas and assumptions

Steady drum solids

BD/S = F/(B − F); cycles = B/F

F is the effective feedwater TDS, B is the drum target and S is dry steam production. Conductivity is multiplied by an editable site factor. Zero feed TDS gives zero calculated continuous blowdown and unlimited theoretical cycles.

Water balance and screening bands

Feed = S + BD; make-up = feed − returned condensate

ABMA screening values are 3,500 ppm through 300 psig, 3,000 ppm above 300 through 450 psig, and 2,500 ppm above 450 through 600 psig. Use the verified OEM or site target when it is more restrictive.

Flash and heat exchanger

f = (h_f,boiler − h_f,receiver)/h_fg,receiver; Q_BD = BD·(h_f,boiler − h_makeup)

Usable vapor yields flash latent heat. The exchanger recovers an entered fraction of the remaining liquid sensible heat relative to make-up. Divide recovered heat by boiler efficiency to estimate fuel avoided.

Worked examples

Open a case to edit its inputs.